Analytic Systems BCA150-12
The BCA150 provides up to 150 watts of precision charging power to up to two battery banks at 12 or 24 volts DC. This unit features universal input voltage, accepting any conventional source of AC power from 85 to 265 volts AC at 50 or 60Hz. Power factor correction technology ensures the most efficient use of this power. The unit can be easily configured for charging standard or deep cycle lead-acid, VRLA, or Gel cell type batteries through use of the output voltage adjust (Over a range of the standard output voltage ±1.0V). User-selectable two-stage or three-stage charging profiles and temperature compensation allow optimum charging of all battery types. Additionally, user-initiated cell equalization and low ripple charging profiles protect and maintain expensive battery systems greatly increase their lifetime usage. Extra input and output filtering reduce EMI to extremely low levels to prevent interference with sensitive communications equipment. Reliability features include an input fuse, thermal shutdown, current limiting, reverse battery hookup protection, and output short circuit shutdown with automatic recovery.
- 150 watts of charging power
- Two or three bank charging
- Temperature compensation
- Manual equalization mode
- Two or three stage charging profiles
- Low EMI
- Adjustable float voltage
- Three year parts and labour warranty
- Typical Service Life : > 10 years (87,600 hrs)
Details
Input Voltage: | 85 - 265 VAC |
Input Current: | 3 Amps with Inrush Protection |
Input Frequency: | 45 - 405 Hz |
Efficiency: | > 90 % at Full Load |
Power Factor: | > 0.98 at Full Load |
Constant Output Voltage: | 12V |
Output Current: | 12A |
Duty Cycle: | Continuous |
Stages: | 2 or 3 stage user selectable |
Operating Temperature: | -25°C to +40°C @ maximum output. Derate Linearly 2.5% per °C from 40°C |
Humidity: | 0 - 95% Relative Humidity (non-condensing) with standard conformal coating |
Switching Frequency: | 50 ± 5% kHz |
Phase: | Single Phase |
Isolation Input-Case: | > 1500 VDC |
Isolation Input-Output: | > 1500 VDC |
Isolation Output-Case: | > 1500 VDC |
Output Fuse: | ATL-15 |
Length: | 20.3 CM |
Width: | 22.4 CM |
Height: | 5.6 CM |
Weight: | 1.6 KG |
Construction
- Material and Finish : Marine Grade Black Anodized Aluminum with 18-8 Stainless Fasteners
- Wall Mount (With Drip Shield)
- Connections : AC Input - IEC Inlet 26.4mm Tab Flange Mount, DC Output - Phoenix VDFK 4 Connector (Black and Red)
Applications
- Military
- Industrial
- Telecommunications
- Transportation
- Alternative Energy
Standards
- Emissions Meets FCC Part 14, Class B
- Warranty : Three Years Parts and Labor
- Safety Built to meet CSA C22.2 No.107.1 and UL 458