Analytic Systems BCD1000-300-48

SKU: BCD1000-300-48-CT-BC-CA
20A, 48V Out, 280-360V In, Iso DC/DC Battery Charger, 2 Bank
Sector:
Material Handling, Switchgear
Need:
Minimum Quantity
1
My Wishlist
Compare
H-14-16w.png
Description

The model BCD1000 Battery Charger charges either 12V, 24V or 48V batteries from a 110, 220 or 300VDC power source. Other battery voltages up to 72 volts are also available by special order.

The all-new Current Mode switching design offers increased power and reliability in a compact package. Extra input and output filtering reduce EMI to extremely low levels. Reliability features include an input fuse, thermal shutdown, current limiting, reverse battery hookup protection, output short circuit shutdown with automatic recovery and an equalize charge mode. The output voltage is easily adjusted 1.0 volts above or below the standard output voltage to accommodate special charging requirements.

Features
  • 1000 watts of charging power
  • Two or three bank charging
  • Temperature compensation
  • Manual equalization mode
  • 1, 2 or 3 bank charging
  • Low EMI
  • Adjustable float voltage
  • Three year parts and labour warranty
  • Typical Service Life : > 10 years (87,600 hrs)

Details

Input Voltage: 280 - 360 VDC
Input Current: 5.3 A
Efficiency: > 80 % at Full Load
Constant Output Voltage: 48V
Output Current: 20A
Duty Cycle: Continuous
Stages: 2 or 3 stage user selectable
Humidity: 0 - 95% Relative Humidity (non-condensing) with standard conformal coating
Isolation Input-Case: > 1500 VDC
Isolation Input-Output: > 1500 VDC
Isolation Output-Case: > 1500 VDC
Input Fuse: MDA-6
Output Fuse: ATC 25 x2
Length: 36.8 CM
Width: 25.1 CM
Height: 14 CM
Weight: 5.5 KG

Construction

  • Material and Finish : Marine Grade Black Anodized Aluminum with 18-8 Stainless Fasteners
  • Four contact output terminals

Applications

  • Military
  • Industrial
  • Telecommunications
  • Transportation
  • Alternative Energy

Standards

  • Emissions Meets FCC Part 14, Class B
  • Warranty : Three Years Parts and Labor
  • Safety Built to meet CSA C22.2 No.107.1 and UL 458