Analytic Systems BCA610-110-48

SKU: BCA610-110-48-CT-BC-CA
11A, 48V Out, 110 VAC In, AC/DC Battery Charger, 2 Bank, CSA/UL
Sector:
Material Handling, Switchgear
Need:
Minimum Quantity
1
My Wishlist
Compare
H-14-16w.png
Description

The traditional BCA610 series chargers feature 600 watts of precision charging power for 1, 2 or 3 banks of batteries at 12, 24, 32, 36, 48 or 72(rail) volts DC. Models are available to operate from 110 or 220 volts AC at 50, 60 or 400 Hz.

All models feature user selectable 2-stage or 3-stage charging profiles, temperature compensation and user initiated equalization for optimum charging and maximum battery life

Features
  • 150 watts of charging power
  • Two or three bank charging
  • Temperature compensation
  • Manual equalization mode
  • Two or three stage charging profiles
  • Low EMI
  • Adjustable float voltage
  • Three year parts and labour warranty
  • Typical Service Life : > 10 years (87,600 hrs)

Details

Input Voltage: 90 - 130 VAC
Input Current: 3 Amps with Inrush Protection
Input Frequency: 45 - 65 Hz
Efficiency: > 90 % at Full Load
Power Factor: > 0.98 at Full Load
Constant Output Voltage: 48V
Output Current: 11A
Duty Cycle: Continuous
Stages: 2 or 3 stage user selectable
Operating Temperature: -25°C to +40°C @ maximum output. Derate Linearly 2.5% per °C from 40°C
Humidity: 0 - 95% Relative Humidity (non-condensing) with standard conformal coating
Switching Frequency: 50 ± 5% kHz
Phase: Single Phase
Isolation Input-Case: > 1500 VDC
Isolation Input-Output: > 1500 VDC
Isolation Output-Case: > 1500 VDC
Output Fuse: AGC-25
Length: 36.8 CM
Width: 25.1 CM
Height: 14 CM
Weight: 3.3 KG

Construction

  • Material and Finish : Marine Grade Black Anodized Aluminum with 18-8 Stainless Fasteners
  • Wall Mount (With Drip Shield)
  • Connections : AC Input - IEC Inlet 26.4mm Tab Flange Mount, DC Output - Phoenix VDFK 4 Connector (Black and Red)

Applications

  • Military
  • Industrial
  • Telecommunications
  • Transportation
  • Alternative Energy

Standards

  • Emissions Meets FCC Part 14, Class B
  • Warranty : Three Years Parts and Labor
  • Safety Built to meet CSA C22.2 No.107.1 and UL 458